首页 | 本学科首页   官方微博 | 高级检索  
     检索      


The Key Parameters Method of Calculating Geothermal Heat Exchanger Length
Institution:College of Power Engineering, Shanghai University of Science and Technology, Shanghai 200093, P. R. China;;College of Mechanical Engineering, Shanghai University of Engineering Science, Shanghai 200336, P. R. China)
Abstract:The geothermal heat exchanger is the key component of ground coupled heat pump systems. We discuss the key parameters method of calculating geothermal heat exchanger length based on line source theory. Typical meteorological year data is used to determine the hottest month, the coldest month and annual average surface temperature. The building hourly load can be obtained by introducing the concept of equilibrium temperature. The cooling fraction and the heating fraction then can be calculated using building hourly load and performance parameters curve fit of a water source heat pump unit. The method for selecting the hottest and lowest entering fluid temperature and calculating the borehole and ground thermal resistance is given. A vertical U tube heat exchanger length calculation procedure is proposed.
Keywords:ground coupled heat pump system  geothermal heat exchanger  typical meteorological year  equilibrium temperature
点击此处可从《保鲜与加工》浏览原始摘要信息
点击此处可从《保鲜与加工》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号