作者姓名:YANG Cui ping  SIMA Wen xi  GU Le guan
摘    要:Considering the importance of 500 kV line and taking 500 kV transmission line in Chongqing as an example, the authors calculate lightning strike outage rate (including return stroke and lightning shielding failure) using regulation method, outage rate of return stroke using travelling wave method, and outage rate of lightning shielding failure using EGM. By comparing and analysing the calculating fesults, weakness of insulation and the area of easy to striking are found out, and corresponding improving measure is brought forward. The results show bigger gradient of lightning higher return stroke tripping, and in regulations result of accounting return stroke tripping is more closed to practical experience, accounting shielding failure rate exists obviously defect, and in EGM accounting shielding failure rate have take much factor, result is more close to practical experience.

关 键 词:return  stroke  lightning  shielding  failure  tripping  out  rate

Lightning Proof Performance of 500 kV Transmission Line in Chongqing Area
YANG Cui ping,SIMA Wen xi,GU Le guan.Lightning Proof Performance of 500 kV Transmission Line in Chongqing Area[J].Storage & Process,2001(5):98-102.
Authors:YANG Cui ping  SIMA Wen xi  GU Le guan
Abstract:Considering the importance of 500 kV line and taking 500 kV transmission line in Chongqing as an example, the authors calculate lightning strike outage rate (including return stroke and lightning shielding failure) using regulation method, outage rate of return stroke using travelling wave method, and outage rate of lightning shielding failure using EGM. By comparing and analysing the calculating fesults, weakness of insulation and the area of easy to striking are found out, and corresponding improving measure is brought forward. The results show bigger gradient of lightning higher return stroke tripping, and in regulations result of accounting return stroke tripping is more closed to practical experience, accounting shielding failure rate exists obviously defect, and in EGM accounting shielding failure rate have take much factor, result is more close to practical experience.
Keywords:return stroke  lightning shielding failure  tripping  out rate
点击此处可从《保鲜与加工》浏览原始摘要信息
点击此处可从《保鲜与加工》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号